LOT 1A
Notes: FOR COLUMN AND RAFTER MARK NUMBERS, SEE MARK NUMBER PLAN.
SPLICE BOLT TABLE
(2) INDICATES THAT FLANGE BRACING IS REQUIRED ON BOTH SIDES OF THE FRAME LINE.
SPLICE
BOLTS
CLEAR TO F.F.
PLATE SIZE
PLATE SIZE
FOR THE EXPANDABLE ENDWALL RIGID FRAMES, IF FLANGE BRACING IS REQUIRED ON BOTH SIDES (2) OF AN EXPANDABLE ENDFRAME, THE OPPOSITE SIDE FLANGE BRACE WILL HAVE TO BE INSTALLED AT THE TIME OF EXPANSION. THESE FLANGE BRACES HAVE BEEN PROVIDED, AS REQUIRED, FOR THIS FUTURE CONDITION.
A
(4) 3/4 X 3 A325T
13'-8 7/8"
5" X 1/4
N/A N/A
B (4) 3/4 X 3 A325T
15'-6 9/16"
5" X 5/16
IF (2) IS NOT INDICATED, ONLY ONE FLANGE BRACE IS REQUIRED AND CAN BE LOCATED ON EITHER SIDE OF THE FRAME.
"*" INDICATES THE LONG SIDE OF THE INTERIOR COLUMNS. COLUMNS AT THE RIDGE ARE TYPICALLY "FLAT-TOP" COLUMNS, UNLESS INDICATED BY THE "*" SYMBOL.
01/10/2022 06:40:45am
RIGID FRAMES SHALL HAVE 50% OF THEIR BOLTS INSTALLED AND TIGHTENED ON BOTH SIDES OF THE WEB ADJACENT TO EACH FLANGE BEFORE THE HOISTING EQUIPMENT IS RELEASED.
12
(972) 524-5407
(972) 524-5417 FAX:
1"
2 2 ' - 5 7 / 1 6 "
PHONE:
1 ' - 4 "
4 ' - 6 "
4 ' - 6 "
4 ' - 6 "
4 ' - 6 "
F B C 4 2
3 ' - 1 7 / 1 6 "
F B C 4 2
F B C 4 2
B
A
CROSS SECTION AT LINE 7 (LOADING DOCK) DRAWING TITLE
PROJECT NAME EMS - Phase II
FLANGE BRACING ATTACHMENT REFER TO AG0110 & AG0160 FOR
T21V0558A ADDRESS
CUSTOMER NAME SIENNA CONSTRUCTION DRAWING STATUS FOR CONSTRUCTION Baton Rouge, LA 70807 4060 T.B. Herndon Avenue
# RELEASE / REVISION DWN / CHK ENG DATE 0 PERMITS CM / ATS BMO 10/05/2021 1 Finals BTW / TJF 01/06/2022 E11 SHEET HAE
JOB NUMBER
16'-8 3/8"
14'-10"
11 7/8"
21'-4 5/8"
B
A
22'-4 1/2"
01/ 18/ 202 2
CROSS SECTION AT LINE 7 (LOADING DOCK)
Made with FlippingBook - Share PDF online